Newsletter 高速鐵路簡訊 . 交通部高速鐵路工程局
機場捷運車站火警偵測系統簡介 Introduction to the Fire Detection and Alarm System in TIAA MRT Stations
機場捷運車站火警受信總機(A18)。

為避免機場捷運車站遭受火災危害,於各車站均設置有火警偵測系統,其主要功能有二:1.當火災發生時,即時偵測發生位置,俾利站務人員採取適當防護措施;2.自動發出火災警報(含警報音響、閃光)及警報訊號,以連動緊急廣播系統通知站內人員及時逃生疏散,同時連動消防滅火系統及排煙設備等,以達成迅速滅火、確保人員逃生安全,有效降低設備財物損失。
在機場捷運各車站之站務室附近均設有智慧型火警受信總機,連接車站範圍所有自動火警探測器、手動報警機及各類消防設備(含自動撒水系統、低污染氣體自動滅火設備(FM200)、排煙設備等)之訊號,以監控車站各區域之火警警報及消防設備之狀態。
倘機場捷運車站發生火災時,車站火警受信總機除會自動發出警報訊號予建築物管理系統(BMS)並連動閉路電視監視系統(CCTV),以利站務人員及時掌握火災情況外,該警報訊號亦會再傳送至中央監控系統,通報行控中心人員採取必要之列車運轉防護措施;另當車站電梯接收到火警警報訊號時,電梯將會自動運轉至安全出口樓層,於開門15~20秒後關閉且停止使用,以利人員逃生及避免誤用。

To prevent fire damage in TIAA MRT stations, each station is equipped with a fire detection and alarm system. The two main functions are first, when a fire occurs, the system can detect the occurrence location for station personnel to take appropriate protective measures; second, the system can automatically send out a fire alarm (including sirens, flashing) and warning signals to interlock with the emergency broadcast system to notify passengers and station staff to evacuate in time while interlocking fire extinguishing system and smoke control equipment, so as to achieve rapid fire extinguishing, ensure personnel evacuation safety and reduce equipment and property damage.
There are Local Fire Alarm Panels (LFAP) installed near passenger agent offices (PAO) to connect signals from automatic fire detectors, manual alarm machine and various types of fire equipment (including automatic sprinkler systems, low-pollution gas automatic fire extinguishing equipment (FM200), exhaust equipment, etc.) in order to monitor fire alarms and fire equipment status in each region of the stations.
During a fire in a TIAA MRT station, the LFAP will automatically send alert signals to the building management system (BMS) and interlock to CCTV surveillance system to facilitate station personnel to grasp the situation of the fire. Simultaneously, the alarm signal will be transmitted to SCADA to notify OCC personnel to take necessary protective measures. On the other hand, when the station elevator receive the fire alarm signal, the elevator will automatically run to a safe exit floor and close the elevator door after 15 to 20 seconds in order to facilitate personnel evacuation and avoid misuse.

  • 機場捷運車站火警受信總機(A21)。
  • 火警受信總機之模擬顯示板。